The distance protection relay used in
this test bench is MiCOM P443. It has 8 CT inputs and 4 PT inputs.
These CT and PT inputs provides the
status of line which is then compared with the protection settings and then
isolate the line from the abnormal condition. The relay has all protection
functions embedded which are processed numerically from current inputs and
voltage input. It has 16 binary inputs optically coupled and 24 binary outputs
which can be used for tripping the breakers etc.
The relay is programmable to suite the
requirement at site. In this panel, the relays are configured or programmed to
suit the testing of all protection functions available in the relay. Before the
start of the relay testing, the protection setting must be completed. The
protection settings for each function such as impedance, for example can be
calculated by considering any conductor of the line say 220kV for instance
Line impedance protection testing
During normal operation these CTs and
PTs provide the current and voltage of the line to the relay which detects the
faults.
From left to right:
Carrier Re-closer Valve
SF6 Loss
Circuit Breaker
Reset Buttons
•Distance (21P/21G)
•Directional and non-directional
Overcurrent (67/50/51 P)
•Directional and non-directional Earth
fault (67N/50N/51N)
•Negative sequence Overcurrent (46)
•Broken Conductor detection (46BC)
•Power swing Blocking (68)
•Out-of-step (78)
•Thermal Overload (49)
•Under-voltage (27)
•Over-voltage (59)
•Under-and Over-frequency (81U/O/R )
•Circuit Breaker Failure (50BF)
•Auto-reclosing (79)
•Check Synchronism (25)
•Fault Locator (FL)
•Event and Trip Logs
Buzzer
The Buzzer will turn on when a fault
happens in the system
The generator protection relay used in
this test bench is MiCOM P343. It is having 8 CT inputs and 4 PT inputs.
These CT and PT inputs provides the
status of generators which is then compared with the protection settings and
then isolate the generator from the abnormal condition. The relay has all
protection functions embedded which are processed numerically from current
inputs and voltage input. It has 16 binary inputs optically coupled and 14
binary outputs which can be used for tripping the breakers etc.
The relay is programmable to suite the
requirement at site. In this panel, the relays are configured or programmed to
suite the testing of all protection functions available in the relay. The relay
outputs and inputs are programmable.
Before start of the relay testing, the
protection setting must be completed. The protection settings for each function
such as differential, impedance, for example can be calculated by considering
any rating of the generator say 84MW for instance
Dummy Circuit Breaker
Simulates the function of a real-time
circuit breaker
Trip Circuit Relay
This is used to reset the numerical
relay after each test
•Genertor Differential (87G)
•Reverse Power (32)
•Field Failure (40)
•Directional and non-directional
Overcurrent (67/50/51)
•Negative sequence Overcurrent (46)
•Thermal Overload (49)
•Underimpedance(21)
•Rotor earth fault protection (64R)
•Third-harmonic type 100% Sator
earthfault (27TN/59TN )
•Out-of-step (78)
•Under-voltage (27)
•Over-voltage (59)
•Negative Phase Sequence (47)
•Under-and Over-frequency (81U/O)
•Circuit Breaker Failure (50BF)
•Check Synchronism (25)
•Event and Trip Logs
This component is used to connect test
signal to the relay from the primary injection kit
Left Inputs
Right Feedback
Buzzer
The Buzzer will turn on when a fault
happens in the system
The bus bar protection relay used in
this test bench is MiCOM P746. It is having 7 CT inputs. In this, only 4 CT
inputs are used in the test bench. These CT inputs provides the status of bus
bar which is then compares incoming R-phase current to outgoing R-phase current
to achieve differential and bias current. These differential and bias current
use for detecting fault and then isolate the bus bar from the abnormal
condition. It also has binary inputs which are optically coupled and binary
outputs which can be used for tripping the breakers etc.
The relay is programmable to suite the
requirement at site. In this panel, the relays are configured or programmed to
suite the testing of all protection functions available in the relay.
Dummy Circuit Breaker
Simulates the function of a real-time
circuit breaker
Control Switches
Test Block
This component is used to connect test
signal to the relay from the primary injection kit
Trip Circuit Relay
This is used to reset the numerical
relay after each test
The transformer protection relay used in
this test bench is MiCOM P642. It is having 8 CT inputs and 1 PT inputs. These
CT and PT inputs provide the status of transformer which is then compared with
the protection settings and then isolate the transformer from the abnormal
condition. The relay has all protection functions embedded which are processed
numerically from current inputs and voltage input. It has 8 binary inputs
optically coupled and 8 binary outputs which can be used for tripping the
breakers etc.
The relay is programmable to suite the
requirement at site. In this panel, the relays are configured or programmed to
suite the testing of all protection functions available in the relay.
Before start of the relay testing, the
protection setting must be completed. The protection settings for each function
such as differential, impedance, for example can be calculated by considering
any rating of the transformer say 20MVA for instance.
Dummy Circuit Breaker
For simulating different protection
functions, such as directional and non-directional faults, broken conductor, and
thermal overload.
From left to right:
Pressure Relief Valve
Oil Temperature Indicator (OTI)
Winding Temperature Indicator (WTI)
Buchholz Relay
Circuit Breaker
Transformer Differential (87T)
•Directional and non-directional
Overcurrent (67/50/51)
•Negative sequence Overcurrent (46)
•Thermal Overload (49)
•Restricted Earth Fault (64)
•Over-fluxing (24)
•Under-voltage (27)
•Over-voltage (59)
•Negative Phase Sequence (47)
•Under-and Over-frequency (81U/O)
•Circuit Breaker Failure (50BF)